R-Value Thermal Resistance Calculator

Thermal resistance, commonly called R-value, quantifies how strongly a material or assembly resists heat flow. The formula is R = L / k, where L is the material thickness (m) and k is the thermal conductivity (W/(m K)). For a wall assembly consisting of multiple layers, the total R-value is the sum of each layer's R-value. A higher R-value means better insulation. This calculator finds the R-value of a single layer and converts between SI (m^2 K/W) and US customary (ft^2 F h/BTU) units, which are widely used by the US DOE and ASHRAE building codes.

4 inches = 0.1016 m; 1 inch = 0.0254 m
Fiberglass batts: ~0.04; wood: 0.12-0.17; concrete: ~1.7
0.00
0.00

R-value formula

R(SI) = L / k R(US) = R(SI) × 5.6783

L is thickness in meters (m), k is thermal conductivity in W/(m K). R(SI) is in m^2 K/W. To convert to US customary R-value (ft^2 F h/BTU): multiply by 5.6783. For layered assemblies: R_total = R1 + R2 + R3 + ...

Worked example

  • 100 mm (0.1 m) of fiberglass batts with k = 0.04 W/(m K).
  • R(SI) = 0.1 / 0.04 = 2.50 m^2 K/W.
  • R(US) = 2.50 x 5.6783 = 14.20 (commonly written R-14).

Frequently asked questions

What is thermal resistance (R-value)?

R-value measures a material's resistance to heat flow. R = L / k, where L is thickness in meters and k is thermal conductivity in W/(m K). A higher R-value means better insulation. In the US building industry, R-values are often stated in customary units (ft^2 F h/BTU).

What are US customary R-value units vs SI?

US customary R-value is in ft^2 F h/BTU (often just called 'R'). SI R-value is in m^2 K/W. To convert: 1 m^2 K/W = 5.678 ft^2 F h/BTU. This calculator uses SI units but shows the US equivalent.

How do R-values add for layers?

For a wall assembly with multiple layers in series, the total R-value is the sum of individual R-values: R_total = R1 + R2 + R3 + ... This makes it easy to calculate the total insulating performance of a multi-layer wall, ceiling, or floor.

What R-values do common materials have?

Fiberglass batt insulation: R-3.2 to R-3.8 per inch (SI: 0.56 to 0.66 m^2 K/W per 25 mm). Foam board: R-3.8 to R-6.5 per inch. Concrete block (8 in): about R-1.1 SI. Double-pane window: about R-0.35 SI. Values from ASHRAE Fundamentals.

What R-values are required by US building codes?

DOE/ASHRAE 90.1 and the IECC prescribe minimum R-values by climate zone. For example, attic insulation ranges from R-30 (warm climates) to R-60 (cold climates) in customary units. The DOE Building Energy Codes Program publishes these requirements.

Official sources

Reviewed by the CalculatorHub team, edited by James Graham, 15 June 2026. See our methodology.