Three-Phase Current Calculator

In a balanced three-phase AC system, the line current drawn by a load is I = P / (sqrt(3) * VL * pf), where P is total three-phase real power in watts, VL is the line-to-line voltage in volts, and pf is the power factor. This formula is essential for sizing conductors, circuit breakers, and motor starters for three-phase equipment. Apparent power is S = sqrt(3) * VL * I. Enter the power, voltage, and power factor to find line current and apparent power.

0.00
0.00

Three-phase power formulas

I = P / (sqrt(3) * VL * pf)
S = sqrt(3) * VL * I (apparent power, VA)
sqrt(3) = 1.7321

Example: P = 15,000 W, VL = 480 V, pf = 0.90. I = 15,000 / (1.7321 * 480 * 0.90) = 15,000 / 748.27 = 20.05 A. S = 1.7321 * 480 * 20.05 = 16,667 VA.

Three-phase current in practice

  • Motor nameplates list full-load amps (FLA) at rated voltage and power factor. Use this calculator to verify sizing or to convert kW to amps for unlabeled equipment.
  • NEC Article 430 requires conductors sized at 125% of motor FLA for branch circuit protection. Calculate FLA first, then multiply by 1.25.
  • Three-phase 480 V systems deliver the same power as 240 V with half the current, significantly reducing conductor cost for long runs.
  • Variable frequency drives (VFDs) may have non-unity power factor on the input; use the VFD's rated input kVA for sizing, not the motor's rated kW output.

Frequently asked questions

What is the three-phase current formula?

For a balanced three-phase system, line current I = P / (sqrt(3) * VL * pf), where P is real power in watts, VL is line-to-line voltage in volts, and pf is power factor. Apparent power S = sqrt(3) * VL * I.

What is the difference between line voltage and phase voltage?

In a three-phase system, line voltage (VL) is the voltage between any two line conductors. Phase voltage (Vphase) is the voltage between one line conductor and neutral. For a balanced star (wye) system, VL = sqrt(3) * Vphase. In the US, 208 V three-phase has 120 V phase-to-neutral.

What is sqrt(3) in the three-phase formula?

The sqrt(3) factor (approximately 1.732) accounts for the 120-degree phase offset between the three phases. When you add three phasors separated by 120 degrees, the result is sqrt(3) times the individual phasor magnitude.

What are common three-phase voltages in the US?

Common US three-phase voltages include 208/120 V (commercial buildings), 240 V (delta, industrial), 480/277 V (large commercial/industrial), and 4,160 V or higher (utility distribution). Industrial motor nameplate voltages are 200, 230, 460, and 575 V.

How does three-phase compare to single-phase for the same power?

Three-phase delivers the same power as single-phase but with lower current per conductor by a factor of sqrt(3) at the same line voltage, reducing conductor losses. It also provides smoother power delivery and is more efficient for large motors.

Official sources

Reviewed by the CalculatorHub team, edited by James Graham, 15 June 2026. See our methodology.