Wire Gauge Calculator (AWG Ampacity)

Choosing the correct wire gauge is a critical safety requirement for any electrical installation. Use the wrong gauge and you risk overheating, insulation damage, and fire. This calculator uses ampacity data from NFPA 70 (the National Electrical Code, NEC) 2023 edition, Table 310.15, for copper conductors in conduit rated at 60 degrees Celsius. Enter the continuous current your circuit must carry and the tool returns the minimum AWG size, its rated ampacity, and its resistance per 1,000 feet. The full NEC reference table is shown below for every gauge from AWG 14 through AWG 4/0. Note that this data applies to standard conditions: a single set of current-carrying conductors in a conduit at an ambient temperature of 30 degrees Celsius. Additional derating is required for high ambient temperatures, multiple conductors in the same conduit, and other conditions specified in NEC Article 310. Always consult a licensed electrician and your local authority having jurisdiction (AHJ) before wiring any circuit.

Continuous current the circuit must carry
Minimum AWG--
Rated ampacity--
Resistance per 1,000 ft--

This tool is for reference only. Always consult the full NEC and a licensed electrician before any electrical installation.

NEC 310.15 ampacity table: AWG 14 to 4/0

Copper conductors in conduit, 60°C rating, ambient temperature 30°C. Data from NFPA 70 (NEC) 2023 edition. Apply derating from NEC Table 310.15(C)(1) for bundled conductors or elevated ambient temperatures.

AWG Max ampacity (A) Resistance per 1,000 ft (Ω)
AWG 14 15 A 3.14 Ω
AWG 12 20 A 1.98 Ω
AWG 10 30 A 1.24 Ω
AWG 8 40 A 0.778 Ω
AWG 6 55 A 0.491 Ω
AWG 4 70 A 0.308 Ω
AWG 3 85 A 0.245 Ω
AWG 2 95 A 0.194 Ω
AWG 1 110 A 0.154 Ω
AWG 1/0 125 A 0.122 Ω
AWG 2/0 145 A 0.0967 Ω
AWG 3/0 165 A 0.0766 Ω
AWG 4/0 195 A 0.0608 Ω

Frequently asked questions

What does AWG stand for?

AWG stands for American Wire Gauge, a standardized wire gauge system used in North America for electrical conductors. The system was established in the 19th century and is now maintained as ASTM standard B258. AWG numbers are assigned based on the number of drawing steps used to produce the wire, so the system is not simply linear.

Why does a larger AWG number mean a smaller wire?

The AWG system is counterintuitive: higher numbers indicate thinner wire. AWG 14 is thinner than AWG 10, and AWG 4/0 (read as four-aught) is the thickest in common residential and light commercial use. The numbering reflects the number of dies the wire is drawn through during manufacture: more draws produce a thinner wire and a higher AWG number. For large conductors above 4/0 AWG, sizing switches to kcmil (thousands of circular mils).

What happens if wire is undersized for the load?

Undersized wire creates excessive resistance, which causes the wire to heat up. This can damage insulation, cause voltage drop at the load, and in severe cases start a fire. The NEC requires wire to be sized so that it does not exceed its rated ampacity under normal operating conditions. Overcurrent protection devices (circuit breakers and fuses) are sized to trip before a conductor is damaged, but they do not substitute for correct wire sizing.

Should I use copper or aluminum wire?

Copper is the standard for most branch circuit wiring because it has lower resistance per cross-section, better corrosion resistance, and a well-established connection system. Aluminum is commonly used for service entrance conductors and large feeders (100A and above) because it is lighter and less expensive per foot. Aluminum wiring requires special connectors rated for aluminum, anti-oxidant compound at connections, and larger conductor sizes compared to copper for the same ampacity. The NEC and local codes govern when each material is appropriate.

What is conduit derating and why does it matter?

When multiple current-carrying conductors are bundled together in a conduit, heat builds up and individual conductors must be derated (their allowable ampacity reduced). NEC Table 310.15(C)(1) specifies derating factors: for 4-6 conductors, derate to 80% of table values; for 7-9 conductors, derate to 70%; and so on. This calculator shows the base NEC 310.15 ampacity for 60 degrees Celsius copper conductors in conduit without additional derating. Always consult a licensed electrician and the full NEC for installation decisions.

Sources

  • NFPA 70: National Electrical Code (NEC) 2023, Table 310.15: nfpa.org.

Reviewed by the CalculatorHub team, edited by James Graham, 14 June 2026. For reference only. Consult a licensed electrician and local codes. See our methodology.